    Description

    The GRV-ITR-12 module is part of the groov EPIC® system. This module has 12 channels of analog to digital conversion that convert resistance to temperature or to Ohms.

    The module is ideal for NTC thermistors commonly used in HVAC, refrigeration, and process control applications. It may also be used with PTC thermistors in resistance sensing applications. The module has 12 channels of analog to digital conversion that convert resistance to temperature or to Ohms. The module reads variable resistance type transducers, with input ranges from 500 Ohms to 400 K Ohms, plus Autorange. You can also select from predefined curves for popular thermistors, as well as create custom curves.

    The GRV-ITR-12 module mounts on a groov EPIC® chassis with a GRV-EPIC-PR1 processor and assorted discrete, analog, and serial groov I/O modules.

    Specifications

    Features

    GRV-ITR-12

    Scaling

    x

    Offset and Gain

    x

    Minimum/Maximum Values

    x

    Average Filter Weight

    x

    Simple Moving Average

    x

    Analog Totalizing

    x

    Problem indication

    x

    Specification

    GRV-ITR-12

    Input Ranges (Ohms)

    400 K, 200 K, 100 K, 50 K, 40 K, 20 K, 10 K, 5 K, 4 K, 2 K, 1 K, 500 Ohms, and Autorange

    Accuracy (Ohms @ Range)

    400@400 K, 200@200 K, 100@100 K, 50@50 K, 40@40 K, 20@20 K, 10@10 K, 5@5 K, 4@4 K, 2@2 K, 1@1 K, 0.5@500 Ohms

    Excitation Current
    (Range & Load Watts Dissipated)

    >7.9 µA (400 K & 25 µW), (200 K & 12.4 µW), (100 K & 6.2 µW), (50 K & 3.1 µW),
    >84.7 µA (40 K & 287 µW), (20 K & 144 µW), (10 K & 72 µW), (5 K & 36 µW),
    >169.2 µA (4 K & 115 µW), (2 K & 57 µW), (1 K & 29 µW), (500 & 14 µW)

    Data Refresh Rate

    950 ms

    Analog Data Filtering

    -3 dB @ 2.4 Hz / -25 dB @ 60 Hz

    Software Data Filtering

    • Simple Moving Average (SMA)
    • Weighted Average
    • SMA (1 to 32 readings)
    • Weighted Average (1 to 4096)

    Step Response Time (to 1%)

    85 ms

    Problem Indication

    out of range

    Isolation (field-to-logic)

    300 V working, 1500 V transient (1 minute)

    Isolation (channel-to-channel)

    300 V between channel group 0–5 & channel group 6–11. None within a group.

    Number of Channels

    12

    Chassis Power Consumption

    1.3 W

    Minimum GRV-EPIC-PR1 Firmware Version

    1.3.0

    Minimum PAC Project Version

    10.2000

    Minimum Library Package for CODESYS Version

    1.0.0.0

    Wire Size

    28–14 AWG

    Torque, connector screw

    2.5 in-lb (0.28 N-m)

    Torque, hold-down screw

    3.5 in-lb (0.4 N-m)

    Temperature (operating)

    -20 °C to +70 °C

    Temperature (storage)

    -40 °C to +85 °C

    Humidity (non-condensing)

    5–95% RH

    Agency Approvals

    UL/cUL(Class 1 Div. 2), CE, ATEX(Category 3, Zone 2), RoHS, DFARS

    Warranty

    Lifetime