AC discrete output, 12 channels, 12-250 VAC, channel-to-channel isolation

Price: $408.00
    Quantity:
    Availability: In Stock
    Usually ships In 24 - 48 hours

    Item #: GRV-OACI-12

    Description

    The GRV-OACI-12 digital output module can switch up to 12 separate 12-250 VAC loads. The module's 12 channels provide channel-to-channel isolation plus 300 volts of transient protection for sensitive control electronics from industrial field signals. To minimize transients during switching, AC outputs are zero voltage turn on and zero current turn off.



    Part of the groov EPIC® system, the GRV-OACI-12 offers a full set of features, including:

    • On/off state
    • Output pulsing
    • On/off totalization
    • Open circuit indication

    Specifications

    FeatureGRV-OACI-12GRV-OACIS-12GRV-OAC-12GRV-OACS-12
    Number of channels12121212
    Channel-to-channel isolationxx
    On/off statexxxx
    Output pulsingx x
    On/off totalizationx x
    Problem indicationx x
    SpecificationGRV-OACI-12GRV-OACIS-12GRV-OAC-12GRV-OACS-12
    Line Voltage12–250 VAC12–250 VAC12–250 VAC12–250 VAC
    Current Rating0.5 A0.5 A0.5 A0.5 AC
    Recommended Max. Fuse (fast) or Circuit Breaker2 A 250 VAC / channel, 6 A 250 VAC common2 A 250 VAC / channel, 6 A 250 VAC common2 A 250 VAC / channel, 6 A 250 VAC common2 A 250 VAC / channel, 6 A 250 VAC common
    Minimum Load Current20 mA20 mA20 mA20 mA
    Output Voltage Drop1 V1 V1 V1 V
    Off-state Leakage at Nominal Voltage - 60 Hz1.25 mA @240 VAC 0.7 mA @ 120 VAC1.25 mA @240 VAC 0.7 mA @ 120 VAC1.25 mA @240 VAC 0.7 mA @ 120 VAC1.25 mA @240 VAC 0.7 mA @ 120 VAC
    Peak Blocking Voltage500 V500 V500 V500 V
    Leakage (mA @ 240 V, 60 Hz)1.01.01.01.0
    Operating Frequency40 to 60 Hz, 400 Hz40 to 60 Hz, 400 Hz40 to 60 Hz, 400 Hz40 to 60 Hz, 400 Hz
    Turn-on Time≤ 1/2 cycle (zero crossing)≤ 1/2 cycle (zero crossing)≤ 1/2 cycle (zero crossing)≤ 1/2 cycle (zero crossing)
    Turn-off Time≤ 1/2 cycle (zero crossing)≤ 1/2 cycle (zero crossing)≤ 1/2 cycle (zero crossing)≤ 1/2 cycle (zero crossing)
    Problem Indicationopen circuitnoneopen circuitnone
    Isolation (field-to-logic)300 V working, 1500 V transient (1 minute)300 V working, 1500 V transient (1 minute)300 V working, 1500 V transient (1 minute)300 V working, 1500 V transient (1 minute)
    Isolation (channel-to-channel)300 V working300 V workingNONENONE
    Number of Channels12121212
    Chassis Power Consumption1.3 W1.3 W1.3 W1.3 W
    Wire Size28–14 AWG28–14 AWG28–14 AWG28–14 AWG
    Torque, connector screw2.5 in-lb (0.28 N-m)2.5 in-lb (0.28 N-m)2.5 in-lb (0.28 N-m)2.5 in-lb (0.28 N-m)
    Torque, hold-down screw3.5 in-lb (0.4 N-m)3.5 in-lb (0.4 N-m)3.5 in-lb (0.4 N-m)3.5 in-lb (0.4 N-m)
    Temperature (operating)-20 °C to +70 °C-20 °C to +70 °C-20 °C to +70 °C-20 °C to +70 °C
    Temperature (storage)-40 °C to +85 °C-40 °C to +85 °C-40 °C to +85 °C-40 °C to +85 °C
    Relative Humidity (non-condensing)5–95%5–95%5–95%5–95%
    Agency ApprovalsUL/cUL(Class 1 Div. 2); CE, ATEX(Category 3, Zone 2), RoHS; DFARS; CB SchemeUL/cUL(Class 1 Div. 2); CE, ATEX(Category 3, Zone 2), RoHS; DFARS; CB SchemeUL/cUL(Class 1 Div. 2); CE, ATEX(Category 3, Zone 2), RoHS; DFARS; CB SchemeUL/cUL(Class 1 Div. 2); CE, ATEX(Category 3, Zone 2), RoHS; DFARS; CB Scheme