Features | Epoxy probe, non-immersion Suited for air temperature | Stainless steel probe, waterproof Suited for air or liquid temperatures | Stainless steel probe, waterproof Suited for air or liquid temperatures |
Input Temperature Range | - 40 ??C to 100 ??C | - 40 ??C to 100 ??C | - 40 ??C to 100 ??C |
Output | 233 ??A @ -40 ??C 373 ??A @ 100 ??C | 233 ??A @ -40 ??C 373 ??A @ 100 ??C | 233 ??A @ -40 ??C 373 ??A @ 100 ??C |
Sensitivity | 1 ??A/??K | 1 ??A/??K | 1 ??A/??K |
Input Response Time (% of Span/?? ??C/??Time) | 5 %/7 ??C/7.8 seconds 20 %/28 ??C/33.6 seconds 63.2 %/88.48 ??C/150 seconds | 5 %/7 ??C/7.8 seconds 20 %/28 ??C/33.6 seconds 63.2 %/88.48 ??C/150 seconds | 5 %/7 ??C/7.8 seconds 20 %/28 ??C/33.6 seconds 63.2 %/88.48 ??C/150 seconds |
Output Accuracy | ??0.5 ??C @ 25 ??C. Factory calibrated. | ??0.5 ??C @ 25 ??C. Factory calibrated. | ??0.5 ??C @ 25 ??C. Factory calibrated. |
Repeatability | ??0.25 ??C | ??0.25 ??C | ??0.25 ??C |
Thermal Time Constant | 2.5 minutes typical (still air) | 2.5 minutes typical (still air) | 2.5 minutes typical (still air) |
Isolation | -- n/a -- | 500 V between metal shell and temperature element | 500 V between metal shell and temperature element |
Pipe Fitting Thread Type | -- n/a -- | 1/4" NPT | 1/4" NPT |
Maximum Liquid Pressure | -- n/a -- | 250 psi | 150 psi |
Maximum Cable Length | >2,000 ft. (610 m.) | >2,000 ft. (610 m.) | >2,000 ft. (610 m.) |
Dimensions (nominal) | Overall length: 39 in. (1 m.) Cylinder tip: 0.7??? (1.78 cm) L, 0.375" (0.95 cm) D | Lead wires: 5 ft. (1.52 m.) Probe diameter: 3/8 in. Probe length: 2 in. (5.08 cm.) | Lead wires: 6 ft. (1.83 m.) Probe diameter: 1/4 in. Probe length: 2.75 in. (6.99 cm) |